How can you tell when a system is low on refrigerant? Running a system check can determine whether that’s the case. Consider this scenario: A service technician installs gauges and thermistors on an R-134a, closed-door, medium-temperature refrigeration system, incorporating a liquid high-side receiver and a thermostatic expansion valve (TXV) as the metering device. Both measured and calculated values are listed in Table 1, along with a detailed system analysis.

 

ANALYSIS

Compressor discharge: This temperature is very high compared to normal system operations. The 195°F discharge temperature is caused by the evaporator and compressor running high superheat along with high compression ratios. When undercharged, do not expect the TXV to control superheat. The TXV may be seeing a combination of vapor and liquid at its entrance, so the evaporator will be starved of refrigerant and running high superheat. The compressor will then see high superheat and, with each compression stroke, will superheat the refrigerant even more.

Compression ratios will also be elevated, giving the system a higher-than-normal heat of compression. Compression ratios will be high from low evaporator pressures, and high compression ratios will give the system very low volumetric efficiencies and cause unwanted inefficiencies with low refrigerant flow rates. The compressor will then have to compress much lower pressure vapors coming from the suction line to the condensing pressure. This requires a greater compression range and a higher compression ratio.

 

MEASURED VALUES
Compressor discharge temperature 195°F
Condenser outlet temperature 78°F
Evaporator outlet temperature 10°F
Compressor inlet temperature 50°F
Ambient temperature 70°F
Box temperature 20°F
Compressor volts 230
Compressor amps Low
Low side (evaporator) pressure 3.94 in. Hg (minus 20°F)
High side (condensing) pressure 86.4 psig (80°F)
 
CALCULATED VALUES
Condenser split 10°F
Condenser subcooling 2°F
Evaporator superheat 30°F
Compressor superheat 70°F

TABLE 1: The measured and calculated values on an R-134a, closed-door, medium-termperature refrigeration system, incorporating a liquid high-side receiver and a thermostatic expansion valve.

View/Download the table as a PDF

 

The greater compression range from the lower evaporator pressure to the condensing pressure is what causes compression work and generates added heat of compression. This increased heat may be seen by the high compressor discharge temperature; however, because of the lower flow rates from the lower volumetric efficiencies, a somewhat low load is seen by the compressor. This low load is what keeps the discharge temperature from getting too hot. In conclusion, higher compression ratios and higher superheats are what cause the discharge temperature to be somewhat high. Remember, the discharge line sees all of the superheat coming to the compressor, the motor heat generated, and the heat of compression.

The limit for any discharge temperature measured 3 inches from the compressor on the discharge line is 225°. The back of the discharge valve is usually 50° to 75° hotter than the discharge line, which would make the back of the discharge valve about 250° to 300°. This could vaporize oil around the cylinders and cause excessive wear. At 350°, oil will break down, and overheating of the compressor will soon occur. Compressor overheating is one of today’s most serious field problems, so try to keep your discharge temperatures below 225° for longer compressor life.

High evaporator superheats: Since the evaporator is starved of refrigerant, there will be high evaporator superheats. In turn, this will lead to high compressor (total) superheats. The receiver will not get enough liquid refrigerant from the condenser because of the shortage of refrigerant in the system, and this will starve the liquid line and may even bubble a sight glass if the condition is severe enough. The TXV will not see normal pressures and may even try to pass liquid and vapor from the starved liquid line. The TXV will also be starved and cannot be expected to control superheat.

High compressor superheats: Again, since the liquid line, TXV, and evaporator are being starved of refrigerant from the undercharge, so will the compressor. This can be seen in the high compressor superheat reading.

Low condenser subcooling: Because the compressor will see very hot vapors from the high superheat readings, the gases entering the compressor will be extremely expanded and have a low density. The compression ratio will be high from the low suction pressure, causing low volumetric efficiencies. The compressor will simply not pump much refrigerant, and all components in the system will be starved of refrigerant. The 100 percent saturated liquid point in the condenser will be very low, which will cause a low condenser subcooling. The condenser will simply not be receiving enough refrigerant vapor to condense it to a liquid and feed the receiver.

Condenser subcooling is a good indicator of how much refrigerant charge is in the system because low condenser subcooling can mean a low charge. A high condenser subcooling can mean an overcharge, but not always. For example, this is not true for capillary tube systems having no receiver because a capillary tube system can run high subcooling simply from a restriction in the capillary tube or liquid line. The excess refrigerant will accumulate in the condenser, causing high subcooling and high head pressures. If a TXV receiver system is restricted in the liquid line, most of the refrigerant will accumulate in the receiver, with a bit in the condenser. This will cause low subcooling and low head pressure.

Low compressor amps: High superheats will cause compressor inlet vapors from the suction line to be extremely expanded, decreasing their density. Low-density vapors entering the compressor will mean low refrigerant flow rates through the compressor. This will cause a low amp draw because the compressor will not have to work as hard compressing the low-density vapors. Low refrigerant flow will also cause refrigerant-cooled compressors to overheat.

Low evaporator pressure: Low evaporator pressure is caused by a starved compressor. The compressor will try to draw refrigerant into its cylinders, but there is not enough to satisfy it, so the entire low side of the system will experience low pressure.

Low condensing pressure: Because the evaporator and compressor are being starved of refrigerant, the condenser will also be starved. Starving the condenser will reduce the heat load on the condenser because it will not see as much refrigerant to reject any heat. With not as much heat to accept — thus reject from the compressor — the condenser will be at a lower temperature. This lower temperature will cause a lower pressure in the condenser because of the pressure/temperature relationship at saturation.

The temperature difference between the condensing temperature and the ambient is called the condenser’s delta T or split. The service industry often refers to this as the condenser split, and it can be calculated as follows:

  condensing temperature
- ambient temperature
= condenser delta T (split)

As the condenser sees less and less heat from the compressor because of being starved from the undercharge of refrigerant, the condenser split will decrease. No matter what the ambient temperature is, the condenser split — that is, the difference between the condensing temperature and the ambient — will remain the same if the load remains the same on the evaporator. However, condenser split will change if the heat load on the evaporator changes. As evaporator heat loads increase, the condenser split will increase, and as evaporator heat loads decrease, condenser splits will decrease.

 

SUMMARY

In summary, here are the seven symptoms or telltale signs of a system low on refrigerant:

  1. Medium to high discharge temperatures;
  2. High evaporator superheat;
  3. High compressor superheat;
  4. Low condenser subcooling;
  5. Low compressor amps;
  6. Low evaporator temperatures and pressures; and
  7. Low condensing temperatures and pressures.

 

Publication date: 7/2/2018