Editor’s note: The August 7 Service Hotline included a question and answer about an old refrigerator. Since that appeared, we have received an additional answer. Here we repeat the original question as well as the latest response.QUESTION:
From Alvertis Bledsoe Marianna, AR
I have a General Electric monitor top refrigerator that is more than 50 years old. The nameplate shows sulfur dioxide was in it. The compressor still works, but there is a hole in the coil due to rust.
I want to know how I can restore this unit. Since sulfur dioxide is no longer available, can I use another refrigerant?
ANSWER:
By Henry Ehrens Senior Engineer Sealed Unit Parts Co. Allenwood, NJ
I actually overhauled a monitor top about 50 years ago. It was a very challenging experience. The following is what you will be up against.
Burnouts
COMMENT:By John Lawler Nu-Calgon
We’re writing in response to the answer provided to the question on burnouts in the Sept. 4News. The solution provided (CF-20) should not be considered the only alternative available.
The question’s parameters of cost effective, safe for the system, environmentally safe, and non-hazardous to people, do not limit the answer to the one provided at the expense of other available solutions. And more importantly, the degree or severity of the burnout will also play a role in selecting a solution.
Many equipment and component people will argue in different directions. Component folks will certainly suggest that multiple oil changes and drier changes comprise the best approach. And equipment people will have their preferred approach that will not include the solution proposed in the original answer.
For that matter, we would certainly propose our own solution, Rx11-flush, as an attractive answer, given its degreasing capabilities, excellent evaporation rate and low boiling point.
The point is that there are options and choices. Any such answer to handling a burnout should definitely urge the reader to identify the cause in the first place, and get it corrected.
COMMENT:
By Virginia KMP
We happened to read in your Sept. 4 issue the question regarding burnout cleanup. The answer given by our good friend Dallas Rohrer was incorrect. In fact there are several products in the marketplace that will serve as compressor burnout clean- up. We at Virginia KMP have a new product that will serve that purpose. The product is named Opti-Flush. I would like to make sure that your readers are informed that CF 20 is not the only one in the market.
New Refrigerants
New RefrigerantsQUESTION:From C. Bernard Middletown, NY
Where can I find the table(s) for the property of saturated liquids and saturated vapors for the new refrigerants?
ANSWER:
By Paul Reed DuPont Wilmington, DE
Information on sources of saturated liquid and vapor properties for new refrigerants are available from refrigerant manufacturers for products of interest. For example, readers can contact DuPont in the United States at 800-234-7882; in Canada at 800-873-7882; or via the Internet at www.suva.com.
Valve Plate
QUESTION:From Eric Hersbrook Eastpointe, MI
I’m not clear on the procedure to inspect or replace a compressor valve plate. Here is my understanding of the process.
1. Close the king valve at the receiver outlet.
2. Jump the terminals or jimmy the low-pressure switch.
3. Pump the low side down to pressure well into a vacuum.
4. Close both the compressor service valves and vent the compressor discharge side into the low side.
5. If the compressor pressure dropped below atmospheric, crack the king valve to allow the pressure to rise slightly above atmospheric before finally isolating the compressor for service.
My misunderstanding lies in steps 4 and 5. In step 4, are the service valves front seated or back seated? I can’t see how the discharge side could vent back to the low side without the service valves being cracked or in mid-position. If they are front seated, the discharge line and suction line will be isolated from the compressor. If they are back seated, the gauge ports will be shut off.
In Step 5, why wouldn’t the compressor pressure be left below atmospheric? You would still have to hook up a recovery machine to recover the refrigerant vapor, wouldn’t you?
ANSWER: By Daniel Kramer, P.E. Patent Attorney and former Chief Engineer, Kramer-Trenton
After pumping the low side into a vacuum, you should front seat only the compressor discharge service valve. Then you could vent the high pressure in the discharge side of the compressor head back into the low side through your gauge set. Keep a plug in the charging hose.
If the pressure in the compressor was still in a vacuum, you could crack the king valve to get the pressure up to zero. Then you would front seat the suction service valve and remove the compressor head.
Proper Cfm
QUESTION:From Gregory Daw Poughkeepise, NY
The basic guideline for determining the proper cfm of a blower unit in a forced hot air furnace, also used for air conditioning, is to use 400 cfm for each ton of cooling (12,000 Btu). How is this calculation affected by the height or vertical rise of the duct system when the blower is in the basement and cooling is required on the first floor, second floor, etc.?
ANSWER:
By Daniel Kramer, P.E. Patent Attorney and former Chief Engineer, Kramer-Trenton
The relative elevation of the ducts in an air conditioning system should not affect the basic cfm requirement at all. However, long ducts with many elbows and braces might require you to employ a higher capacity blower to get a desired airflow.
You would have to consult a duct chart and read from it the pressure drop per 100 equivalent ft of duct of your size with your desired airflow. The equivalent length of the various fittings and registers are available from charts and should be added to the actual duct length.
Then, knowing the total pressure drop in inches water gauge that your duct with its fittings would impose, you could enter the chart for your blower to determine what you had to do to get the desired cfm.
The Refrigeration Service Engineers Society Service Applications Manual Section 56 has substantially all the data you would need for this purpose. RSES can be reached at 847-297-6464; www.rses.org (website).