In this month’s troubleshooting situation, our customer has called to say that the older package unit that heats and cools his office is managing to warm up the area, but then seems to cool down too much before providing heat again. When you arrive, the first thing you note is that the indoor blower motor is operating, and you check the fan switch setting on the thermostat.
Bob got a call from the dispatcher to go to an office building that has a 3-ton heat pump compressor that has been shutting off after startup. The fan would continue to run. The building maintenance man said that he had observed the shutting down of the compressor several times.
This article is part one of a two-part series on ice flake
machine troubleshooting. This article will examine troubleshooting low and high
water levels. Next month’s article will examine water impurities and mechanical
problems.
Bob has gone on a service call where the customer is complaining that her house is not getting up to temperature. The house was heated with a heat pump with three stages of auxiliary strip heat. Bob removed the panel to the strip heat and found one of the units was not pulling current.
This troubleshooting situation is a look ahead to the upcoming cooling season. Our customer has called to say that their heat pump “isn’t cooling at all,” and while the outdoor temperature is only in the mid 80’s, it’s quite uncomfortable in the house. You find that the underlying reason is that the compressor and outdoor fan motor aren’t operating.
Troubleshooting and servicing refrigeration and air conditioning systems can be a challenging process for entry-level or experienced technicians. Regardless of your experience, it is essential that you have a solid understanding of the fundamentals. You also need to have the right tools.